De-energized linear tap changer

WST (WDT)  de-energized, linear tap changer

w1b2y

ZH2:De-energized combined linear triple-phase tap changer (a 1set for 2 pieces combination)
Sample:WSTⅣ63/10-6×5ZH2
It is combined by 2 operating pieces of a WSTⅡ63/10-6×5 and a WSTⅣ63/10-3×2
ZH3: De-energized combined linear triple-phase tap changer (1 set for 3 pieces combination)
Sample:WSTⅤ63/20-6×5 ZH3
It is combined by 2 operating pieces of a WSTⅤ63/20-5×2 and 2 WSTⅡ63/20-6×5
F:--- Reversing installed linear switch
G:---Switch for dry-type transformer 
D:---double-sealed switch(Each one on the top of and below the tank cover of transformer)

Technical Data

The tap changer applies to single-phase , triple-phase oil-insulated transformers of the frequency 50Hz, 60Hz, of the highest voltage for equipment 10KV-35KV, of the rated through-current 30A-500A,fixed on tank cover of transformers directly and exchanged in the de-energized state. Voltage regulation positions (center, terminal, neutral point).


Specificatons WST WST WST 125 WST 250 WST 400 WST 500
30 63 125 250 400 500
Connection mode Central point(Ⅱ)Neutral Point(Ⅲ)Terminal Point(Ⅰ)
Rated throughcurrent(A) 30 63 125 250 400 500
Short-circuit capacity Heat stableness current(kA/2s) 0.7 1.6 2.5 3.75 4 5
Dynamic stableness current(kA) 1.8 4 6.25 9.375 10 12.5
Rated frequency(Hz) 50~60
Insulation level(kV) Highest voltage(kV) 10kV 20kV 35kV
Power-frequency withstand Voltage(50Hz/1min) 42kV 55kV 95kV
Impulse(1.2/50μs) 75kV 125kV 250kV
Sealing Performance(kPa/24h) 60
Machine life(Thousands of times) 2
Thickness of transformer tank cover: (1)Opening holeΦ20.5+0.5Applying to3~8mm tank cover;(2)63/10~20        Applying to 5~8mm tank cover;(3)125/10~20       Applying to 6~10mm tank cover;(4)250/10~20       Applying to 8~12mm tank cover;(5)35kV Applying to 8~12mm tank cover