De-energized linear tap changer
WST (WDT) de-energized, linear tap changer

ZH2:De-energized combined linear triple-phase tap changer (a 1set for 2 pieces combination)
Sample:WSTⅣ63/10-6×5ZH2
It is combined by 2 operating pieces of a WSTⅡ63/10-6×5 and a WSTⅣ63/10-3×2
ZH3: De-energized combined linear triple-phase tap changer (1 set for 3 pieces combination)
Sample:WSTⅤ63/20-6×5 ZH3
It is combined by 2 operating pieces of a WSTⅤ63/20-5×2 and 2 WSTⅡ63/20-6×5
F:--- Reversing installed linear switch
G:---Switch for dry-type transformer
D:---double-sealed switch(Each one on the top of and below the tank cover of transformer)
Technical Data
The tap changer applies to single-phase , triple-phase oil-insulated transformers of the frequency 50Hz, 60Hz, of the highest voltage for equipment 10KV-35KV, of the rated through-current 30A-500A,fixed on tank cover of transformers directly and exchanged in the de-energized state. Voltage regulation positions (center, terminal, neutral point).
| Specificatons | WST | WST | WST 125 | WST 250 | WST 400 | WST 500 | |
| 30 | 63 | 125 | 250 | 400 | 500 | ||
| Connection mode | Central point(Ⅱ)Neutral Point(Ⅲ)Terminal Point(Ⅰ) | ||||||
| Rated throughcurrent(A) | 30 | 63 | 125 | 250 | 400 | 500 | |
| Short-circuit capacity | Heat stableness current(kA/2s) | 0.7 | 1.6 | 2.5 | 3.75 | 4 | 5 |
| Dynamic stableness current(kA) | 1.8 | 4 | 6.25 | 9.375 | 10 | 12.5 | |
| Rated frequency(Hz) | 50~60 | ||||||
| Insulation level(kV) | Highest voltage(kV) | 10kV | 20kV | 35kV | |||
| Power-frequency withstand Voltage(50Hz/1min) | 42kV | 55kV | 95kV | ||||
| Impulse(1.2/50μs) | 75kV | 125kV | 250kV | ||||
| Sealing Performance(kPa/24h) | 60 | ||||||
| Machine life(Thousands of times) | 2 | ||||||
| Thickness of transformer tank cover: (1)Opening holeΦ20.5+0.5Applying to3~8mm tank cover;(2)63/10~20 Applying to 5~8mm tank cover;(3)125/10~20 Applying to 6~10mm tank cover;(4)250/10~20 Applying to 8~12mm tank cover;(5)35kV Applying to 8~12mm tank cover | |||||||