Off circuit disc type tap changer
WSP(WDP)off circuit disc type tap changer

This tap changer is a product jointly designed by relevant manufacturers organized by Shenyang Transformer Research Institute. It adopts new structure, new materials, and new technology. It has the advantages of reasonable structure, good hand feel, flexible gear adjustment, and accurate positioning. It is the current updated product of my country's non-excitation tap changer. It is suitable for single-phase and three-phase oil-immersed power transformers with frequencies of 50HZ and 60HZ, rated voltages from 10kV to 35kV, and rated currents from 63A to 250A. It can be directly fixed on the transformer box cover.
Technical Parameters
Specificatons | WSP 63 | WSP 125 | WSP 250 | |
Phase number | three-phases | |||
connection mode | Central point(Ⅱ)Neutral Point(Ⅲ) | |||
Rated through current(A) | 63 | 125 | 250 | |
Short-circuit capacity | (kA/2s)Heat stableness current(kA/2s) | 1.6 | 2.5 | 3.75 |
(kA) Dynamic stableness current(kA) | 4 | 6.25 | 9.375 | |
Rated frequency(Hz) | 50~60 | |||
Insulation level(kV) | Rated Voltage(kV) | 10kV | 20kV | 35kV |
Power-frequency withstand Voltage(50Hz/1min) | 42kV | 55kV | 95kV | |
Impulse(1.2/50μs) | 75kV | 125kV | 250kV | |
Sealing Performance(kPa/24h) | 60 | |||
Machine life(Thousands of times) | 2 | |||
Tank hole thickness:(1)63/10~20 tap changer suitable for 5~8mmtransformer tank hole (2)125/10~20 tap changer suitable for 6~10mmtransformer tank hole (3)250/10~20 tap changer suitable 8~12mm transformer tank hole (4)35kV tap changer suitable for 8~12mm transformer tank hole |
Transformer Positioning Welding Assembly Drawing