SYJZZ 200/10 – 9 On Load Tap Changer (OLTC)
These instructions apply to tap-changers rated at 10 kV, with rated through-currents of 400 A, 300 A, 200 A, 100 A and below 100 A.
Tap-changers with a rated voltage of 10 kV or less are designed for installation on 50 Hz AC oil-immersed transformers whose primary side rated line voltage is 10 kV and rated through-current is 400 A or lower. They are a core component of on-load voltage regulating transformers.
This switch shall be equipped with a matching on-load tap-changer controller as its operating control unit.
Its main function is as follows: under the transformer’s on-load operating condition, the tap-changer’s tap contacts are connected to the tapping points on the transformer’s high-voltage winding. Responding to signals from the controller, the switch automatically shifts tap positions to alter the turns ratio between the high-voltage and low-voltage windings. This stabilizes or adjusts the voltage at the load center, improves voltage quality and system power factor, and cuts reactive power consumption effectively.
The on-load voltage regulating controller supports manual operation. It can also perform tap change automatically based on deviation signals of the secondary-side voltage (rated 400 V) and automatic operation commands.
The rated working current: 400A, 300A, 200A, 100A and under;
The rated working voltage: 10KV;
The maximum grading Voltage: 600V;
The amplitude of grading voltage-regulation is 2.5%~5%.
- The minimum ambient temperature is -25℃, the maximum ambient temperature is +40℃.
- The minimum temperature of the transformer oil is -25℃, the maximum temperature of the transformer oil is +100℃,at the same time can not be affect with damp.
- The slop of the installation place of the switch and the vertical face shall not be over 5 degrees.