- On-Load Tap Changer
-
D-energized tap changer
- De-energized plate tap changer all excellent
- De-energized WDT. W(1+2) linear tap changer(110KV or less) all excellent
- De-energized drum cylindrical tap changer all excellent
- De-energized manual cage tap changer
- Off circuit cage type tap changer
- De-energized linear tap changer
- Off circuit disc type tap changer
- Controller In General
- Transformer Attachment
0102030405
Vertical electric cage tap changer neutral point
Model Meaning
Advantages
1. The adaptability of this technology makes it suitable for all non-excitation transformers.
2. It has strong anti-short circuit ability and can be used as a high-current high-voltage tap changer
3. The product supports multiple operating modes, allowing for both automatic and manual control.
Details
Connecting method | Neutral point voltage regulation |
Rated current | 200A-1250A |
Rated voltage | 10kV、35kV、66kV、110kV |
Number of positions | 5-16 |
Vertical cage tap changer neutral point is the most advanced solution for managing the neutral point of distribution systems. This innovative device is designed to provide seamless, efficient control of neutral points, ensuring optimal performance and reliability of the distribution network.
One of the main features of the vertical cage tap-changer neutral point is its vertical design, which allows easy installation and integration into existing distribution systems. This compact design also ensures that the device can be easily adapted to a variety of space-constrained environments, making it an ideal solution for retrofitting or upgrading existing power distribution infrastructure.
The electric cage tap-changer technology used in this product ensures smooth and precise neutral point adjustment, providing unparalleled control and flexibility for distribution management. This enables operators to fine-tune the neutral point to meet the specific requirements of their distribution network, thereby improving efficiency and performance.
Voltage Regulation Principle
Outline 1
Transformer tank opening holeΦ380
Type and install measurement 1
Type | Install measurement mm | Frequency withstand level(kV/1min) | |||||
L1 | L2 | H1 | H | To ground | Between phase | Between contacts | |
WSLⅢDL200~630/10-5×5~12×12 | 150 | 110 | 480 | 720 | 45 | 18 | 18 |
WSLⅢDL800~1000/10-5×5~10×10 | 170 | 130 | 550 | 790 | |||
WSLⅢDL200~630/35-5×5~9×9 | 210 | 170 | 650 | 890 | 100 | 45 | 30 |
WSLⅢDL800~1000/35-5×5~8×8 | 210 | 170 | 650 | 890 |
Outline 2
Transformer tank cover opening holeΦ460
Type and install measurement 2
Type | Install measurement mm | Frequency withstand level(kV/1min) | |||||
L1 | L2 | H1 | H | To ground | Between phase | Between contacts | |
WSLⅢDL200~400/10-13×13~16×16 | 150 | 110 | 480 | 720 | 45 | 18 | 18 |
WSLⅢDL630/10-11×11~15×15 | 150 | 110 | 480 | 720 | |||
WSLⅢDL800~1000/10-11×11~12×12 | 170 | 130 | 550 | 790 | |||
WSLⅢDL200~400/35-11×11~16×16 | 210 | 170 | 650 | 890 | 100 | 45 | 30 |
WSLⅢDL630/35-11×11~15×15 | |||||||
WSLⅢDL800~1000/35-11×11~12×12 |