W (1+2) star-delta transformation(Y-△)(Ⅳ)de-energized tap changer

De-energized drum cylindrical tap changer all excellent

W (1+2) star-delta transformation(Y-△)(Ⅳ)de-energized tap changer

Suitable for oil-insulated transformers with a maximum voltage grade of 220kV or lower and a rated through-current of 3000A or lower, this series enables tap changing in the de-energized state of the transformer. It provides the capability to adjust the effective turns of the transformer coil, thereby changing the transformer ratio and stabilizing the output voltage.

    Model Meaning

    w1lru

    For example:W(1+2)ZⅡ630/40.5-6X5 S(Y)C W model is de-energized triple-phase cylindrical middle single bridge span, rated through-current 630 A, highest voltage for equipment 40.5kV, manual (with remote gear display), side operation, 6 tap, 5 gears, horizontal installation.

    Advantages

    1.Designed with simplicity in mind, the product has a compact installation size and can be installed flexibly.
    2.Designed for a strong operation feel, the product ensures reliable contact and minimizes the possibility of misoperation. 
    3.Designed with an automatic reset feature, the contact resets automatically.
    4.With a miniaturized transformer design and simplified tap changer and transformer connection, the electric field distribution is uniform, allowing for flexible layout configurations.

    Advice for user selection and Utilization
    Its body and operation parts are created independently, and there are several and varied ways to install it. In making your pick, kindly consider both the body model and the necessary working mechanism.
    Lead and an actuated insulating rod are included as standard. Please include in the order notification and contract any special requirements. Before installation and usage, the operational insulation rod should be dried with the switch. Once dried, it is ready for use. If there are any specific needs, please take note of the thickness of the insulating paper covering the lead wire.
    The neutral point connection technique of the transformer is not denoted by any symbol in the basic model.
    A 20% margin should be reserved while choosing its current level, and a similar margin should be included.
    The voltage level chosen must satisfy the power frequency and impact specifications for both longitudinal and main insulation.

    Please specify any special requirements.
    Please request the electronic drawing (in PDF or DWG format) and order specification before placing an order.
    The clamp tap changer must be installed with both the transformer gripper and the clamp firmly in place. If not, the vibration will cause the clamp's body to move downward, triggering the control lever clutch.
    For the radial outlet switch, it is not permitted to force the wiring tap lead root bending wire; instead, lead bending should follow the method of static rolling; the root insulation will bend after lead, so please bandage. For the tap changer and transformer coil tap connection, please connect to its body on the transformer.
    Avoid harming the switch by using enough lubricant once it has dried.Its body and operating mechanism are distinct, and during the drying process, the operating mechanism is not dried.
    It has a mechanical limit built into its operating mechanism. To prevent damage, do not go above the switch limit gear. When working, kindly utilize the impact force operation.
    Please remove the mechanism during operation or the transmission mechanism during the core inspection or field debugging, mark before disassembly, and check the DC resistance and variable ratio to confirm correct installation.

    Model Main Technical Specification

    Main performance parameter insulation level(kV) Seal function machinery life span (Time) Rated through-current (A) Short-circuit capacity
    Highest working voltage(KV) Connection method power frequency (1min) Impact(1.2/50μs) Thermal stability(3s)(kA) Dynamic stability(kA)
    To ground Between phase Between contacts Between the first and last To ground Between phase Between contacts
    12 (Y,△) 45 45 20 100 100 70 0.25MPa 24h 2000 250 5 12.5
    40.5 Y 100 40 30 230 120 90 400 6 15
    100 100 30 230 230 90 630 7.5 18.75
    72.5 Y 160 100 30 230 230 90 800 8 20
    160 160 45 350 350 150 1000 10 25
    126 Y 230 140 45 550 350 150 1250 12.5 31.25
    230 230 55 550 550 175 1600 16 40
    252 460 * 90 1050 285 2000 20 50

    Schematic Diagram

    w2dwg

    Outline

    W (1+2) Z star-delta transformation(Y-△ )(Ⅵ)outline install measurement drawing.
    "D" phase(1 phase)clamp-type installation; "L" phase(2phase)clamp-type installation.

    Typical installation measurement Voltage kV Current A Gear Outline, installation measurement mm
    D1 D2 D3 d
    W(1+2)Ⅳ250~630/12-3X2 12 250、400、400、630 2 180 190 D2 + d + δ, δ 40 to 50, where the larger the δ, the more convenient the bending of the lead. 1.5s + package insulation thickness S is the lead cross-sectional area (mm2)
    W(1+2) Ⅳ250~630/40.5-3X2 40.5 200 217

    Notice:Dimensions of 12kV and 20kV are consistent with 40.5kV size class, and 72.5kV size is consistent with 126kV class size. If there are special requirements, please give special instructions when ordering.


    Outline Diagram of the Operating Mechanism

    (1)Manual Operation(SS)

    w35jp

    (2)Manual Operation(Remote gear display)  S(Y)S

    w4wnsw5idi

    (3)Manual side operation(SC)

    e1hbve2n5b

    (4)Electric side operation(DC)

    e3liue4mom
    Read more